| Operating Voltage |
12VDC ±10%, 24VAC ±10% 50/60 Hz., 115V/230V
AC ±15% 50/60 Hz. (The 115V/230V model is operating voltage switch selectable) |
| Operating Power |
7.2 watts maximum. |
| Timing Mode |
7 day - 24 hour programmable On - OFF. |
| Timing Accuracy |
Time-Of-Day to ±2 minutes per month. |
| Programmable Outputs |
Two (2) SPST-NO contacts. Contacts Close at
the scheduled event ON time, open at the scheduled event OFF time |
| Programmable Events Per Output |
Eight (8) events per day. A schedule to turn
one relay ON = 1 event, to turn it OFF = 1 event, with a maximum of 56 events per week.
Two relays scheduled either ON or OFF at the same time is = 1 event. |
| Timing Tolerance |
Based on the scheduled and displayed
time-of-day. |
| Repeatability Of Event Timing |
Based on the scheduled and displayed time-of-day. |
| Output Rating |
UL/CSA rated for 1 HP, 20A 250V AC, 1.5 HP,
20A 125V AC. 1000V rms breakdown voltage between open contacts, 1500V rms breakdown
voltage between all contacts and operating voltage terminals. Insulation resistance
1000M½ at 500V DC. Mechanical Life Expectancy 106 operations, Electrical Life
Expectancy resistive load 105 operations at 20A 250V AC, 1.5 x 103 operations
inductive load (cos = 0.7) steady 20A 250V AC inrush 80A. |
| Digital Display |
Four (4) digit red LED, 0.5 inch high
characters displays, time-of-day, day-of-week, and all event schedules. |
| Time-Of-Day |
Displayed and set in 24 hour format. 6PM =
18:00, 11:00PM = 23:00 etc.. Time-Of-Day is maintained in a smart timepiece circuit that
will keep the time running for up to 5 days during a power failure. No batteries required,
or embedded. |
| Program Memory |
EEPROM type maintains the programmed schedules
for up to 10 years without battery backup. |
| Front Panel Switches |
Tactile type keypad, 0 - 9, *, and #. |
| Transient Protection |
Protected by silicon transient suppressors
which respond to transients within 1 x 10-12 seconds to a peak pulse power dissipation of
1500 watts, with transient surge currents to 200 amperes for durations up to 1/120 second
at 25 deg C. Maximum transient voltage protection is 6000 volts as delivered through a
source resistance of 30 ohms with a maximum duration of 8.3 milliseconds. |
| Operating Temperature |
0 deg.C to +70 deg.C. |
| Mounting |
2.62 X 4.50 cutout accepts timer. Timer
secured with attached bracket and nut. (hardware is provided for mounting) |
| Wiring |
.25 Quick Connects are provided for relay
interface and operating voltage. DC model is non-polar. |
| Programming Handbook |
A comprehensive handbook is supplied with each
model. The handbook provides all instructions, with examples, necessary to operate and
program the model 4950PM. |