Description
The model 438FI (Fixed Interval Time Capsule) is an all Solid State In-Line timing
device providing Interval timing control of any
load device operating from 115 or 230V AC or DC. Timing is factory fixed from 250
milliseconds to 1000 seconds. When power is applied, the 438FI turns "On"
permitting full load current to flow. At the end of the preset timing period the 438FI
turns "Off" and permits only leakage current to flow through the load. Then
interval timing action can be repeated by removing and re-applying the operating voltage.
Specifications
| Operating Voltage |
115 or 230VAC or DC |
| Frequency |
50/60 Hz for AC inputs. |
| Output |
0.25 ampere inductive with inrush currents to 8 amperes for
8 milliseconds. 10 volt maximum drop across timer when output is ON, 3 mA leakage current
through timer when output is OFF. |
| Timing Mode |
In-Line Interval |
| Timing Range |
Factory fixed from 250 milliseconds to 1000 seconds. |
| Timing Repeatability |
+/- 1% at stabilized operating voltage and temperature. |
| Transient Protection |
6000 volts as delivered through a source resistance of 30
ohms with a max duration of 8.3 milliseconds. |
438FI Specifications , click to view,
right click - Save As ... to download.
Ordering Information
| Model |
Voltage |
Time Delay |
| 438FI |
-115 (105-135VAC)
-230 (200-277VAC) |
Specify from 250 milliseconds to 1000 seconds |
Example : 438FI-230-40 operates on 230VAC