Description
The 2600SA is an ON/OFF cycle timer controlling a DPDT set of relay contacts. The 2600SA is
available in a range of both AC and DC models. When operating voltage is applied to the
timer the output contacts transfer initiating the ON portion of the cycle. At the end of
the ON timing period the contacts de-energize and the OFF timing period begins. At the end
of the OFF timing period the cycle repeats for as long as the operating voltage is
applied. The 12 position DIP switches allow for selection of time range and
time period for both the ON and OFF times, allowing different ranges for
each.
Specifications
| Timing Mode |
On/Off Repeat
Cycle Timing |
| Operating Voltage |
12, 24V DC or 24, 115V AC. |
| Adjustable Timing Ranges |
0.1 - 102.4 seconds, 1 - 1024 seconds, 1
- 1024 minutes, 1 - 1024 hours |
| Purchase Tolerance |
±2% |
| Repeatability Of Timing Periods |
Better than ±2% |
| Timing/Temperature Coefficient |
Better than ±0.1% / °C |
| Output Relay |
SPDT contacts - 12A at 125V AC UL E88991 & CSA
LR90143, 10A 125V AC TUV R9452021. |
| Terminations |
Octal plug-in type. |
| Dielectric |
1,200V rms between open contact sets, 1,500V rms between
contacts and operating voltage terminals. |
| Transient Protection |
Protected by silicon transient suppressors responding to
transients within 1x10-12 seconds to a peak pulse power dissipation of 1500 watts. |
| Operating Temperature |
0°C to +65°C |
2600SA Specifications
: (153k) click to view , right click - Save As ... to download.
Ordering Information
| Model |
Operating Voltage |
| 2600SA |
-2 12VDC
-3 24VDC
-6 24VAC
-8 115VAC |
Example : 2600SA-3 operates on 24VDC |