Description
The 2600 is an ON/OFF cycle timer controlling a DPDT set of relay contacts. The 2600 is
available in a range of both AC and DC models. When operating voltage is applied to the
timer the output contacts transfer initiating the ON portion of the cycle. At the end of
the ON timing period the contacts de-energize and the OFF timing period begins. At the end
of the OFF timing period the cycle repeats for as long as the operating voltage is
applied.
Specifications
| Timing Mode |
ON - OFF Repeat
Cycle Timing |
| Operating Voltage |
12, 24V DC or 24, 115V AC. |
| Adjustable Timing Ranges |
0.1 - 30.0 seconds, 2 - 1000 seconds, 30 - 8000 seconds. |
| Purchase Tolerance |
Low time +0%, -50%, High time -0%, +30%. Example - Timing
range -3, (2 - 1000 seconds), can range from 1 to 1300 seconds, with 2 - 1000 seconds as a
guaranteed minimum range. |
| Repeatability Of Timing Periods |
±2% |
| Timing/Temperature Coefficient |
±0.25%/deg.C |
| Output Relay |
SPDT contacts - 12A at 125V AC UL E88991 & CSA
LR90143, 10A 125V AC TUV R9452021. |
| Terminations |
Octal plug-in type. |
| Dielectric |
1,200V rms between open contact sets, 1,500V rms between
contacts and operating voltage terminals. |
| Transient Protection |
Protected by silicon transient suppressors responding to
transients within 1x10-12 seconds to a peak pulse power dissipation of 1500 watts. |
| Operating Temperature |
0 deg.C to +70 deg.C |
2600 Specifications
: click to view , right click - Save As ... to download.
Ordering Information
| Model |
Operating Voltage |
Timing Range |
| 2600A |
-2 12VDC
-3 24VDC
-6 24VAC
-8 115VAC |
-1 0.1-30 seconds
-3 2-1000 seconds
-5 30-8000 seconds |
Example : 2610A-3-1 operates on 24VDC with
time delays from 0.1-30 seconds |