Description
The 2410 is a delay-on-make
timer controlling a DPDT set of relay contacts. The 2410 is available in a range of both
AC and DC models. When operating voltage is applied the timing period begins. At the end
of the timing period the output contacts transfer and remain transferred for a long as the
operating voltage is applied. To recycle the timer the operating voltage must be removed
and re-applied.
Specifications
| Timing Mode |
Delay-On-Make |
| Operating Voltage |
12, 24V DC or 24, 115V AC. |
| Adjustable Timing Ranges |
0.1 - 30.0 seconds, 2 - 1000 seconds, 30 - 8000 seconds. |
| Purchase Tolerance |
Low time +0%, -50%, High time -0%, +30%. Ex: Timing range
-3, (2 - 1000 seconds), can range from 1 to 1300 seconds, with 2 - 1000 seconds as a
guaranteed minimum range. |
| Repeatability Of Timing Periods |
±2% |
| Timing/Temperature Coefficient |
±0.25%/deg.C |
| Recycle Time |
Operating voltage must be removed for a minimum of 100
milliseconds to assure that the timing circuits are reset. |
| Output Relay |
DPDT contacts - 12A at 125V AC UL E88991 & CSA
LR90143, 10A 125V AC TUV R9452021. |
| Terminations |
Octal plug-in type. |
| Dielectric |
1,200V rms between open contact sets, 1,500V rms between
contacts and operating voltage terminals. |
| Transient Protection |
Protected by silicon transient suppressors responding to
transients within 1x10-12 seconds to a peak pulse power dissipation of 1500 watts. |
| Operating Temperature |
0 deg.C to +70 deg.C |
2410 Specifications : click to view , right click to download.
Ordering Information
| Model |
Operating Voltage |
Timing Range |
| 2410A |
-2 12VDC
-3 24VDC
-6 24VAC
-8 115VAC |
-1 0.1-30 seconds
-3 2-1000 seconds
-5 30-8000 seconds |
Example : 2410A-8-5 operates on 115VAC with
time delays from 30-8000 seconds |